Low voltage switchgearMNS Light F and MNS Light SRCatalogue 1TSC2210-EN, ed. 2ABB LV Systems
10MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Supply cubicleDesignThe supply cubicle is manufactured according to SS 436 2131,
11MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Supply cubicleOptionsShort-circuit strength 50 kA ...
12MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Busbar trunking systemDesignThe busbar trunking system is used for incoming or o
13MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Busbar trunking systemType 461 Type 462Size Type name Type nameA1250 (900 for IP
14MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999DesignThe cubicles are designed for withdrawable air circuit-breakers (ACB) in s
15MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Circuit-breaker cubicle ACB with circuit-breaker Megamax3-pole 4-poleSize Type
16MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999OptionShort-circuit strength 50 kA... +M50Isolated
17MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999DesignThe cubicles are designed for withdrawable air circuit-breakers (ACB) in s
18MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Circuit-breaker cubicle ACB for circuit-breaker EmaxFor circuit-breaker 3-pole 4
19MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Circuit-breaker cubicle ACB for circuit-breaker EmaxBreaker Protection Breaking
2MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999General Description ...
20MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999OptionsShort-circuit strength 50 kA... +M505-wire
21MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999DesignThe cubicle is designed for withdrawable or fixed mountedcircuit-breakers
22MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Circuit-breaker cubicle MCCBFixed breaker Fixed breaker Withdraw. breaker Withdr
23MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999OptionsShort-circuit strength 50 kA ... +M505-wire
24MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Disconnector cubicleDesignThe cubicle is available in two sizes from 1250 to 200
25MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Disconnector cubicle3-pole 4-poleSize Type name Type nameA1250 (1000 for IP43/54
26MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999OptionsShort-circuit strength 50 kA... +M505-wire
27MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999DesignThe cubicle consists of a 600 mm wide compartment fordistribution units an
28MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Cable duct for auxiliary circuits ... +C2Placed in the cabl
29MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Apparatus cubicle for F-unitsType namePlaced at bottom (under the normal equippi
3MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999DescriptionApparatus cubicle with SR-u nits (SlimLine).Apparatus cubicle with F-u
30MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Motor starters, pole-changing starters, contactor groupsUnits are available in s
31MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Apparatus cubicle for F-unitsOverview distribution unitsFixed circuit-breaker. P
32MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Rated current 1)Breaking capacity 3-pole 4-poleat 400, 500, 690 V Type name Type
33MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Rated current 1)Breaking capacity 3-pole 4-poleat 400, 500, 690 V Type name Type
34MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Incoming units with MCCB, withdrawable circuit-breaker3-pole4-poleOptionsCurrent
35MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Rated current 1)Fuses with 3-pole 4-poleA max. power dissipation, W Type name Ty
36MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Rated current 1)Breaking capacity 3-pole 4-poleat 400, 500, 690 V Type name Type
37MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Rated current 1)Breaking capacity 3-pole 4-poleat 400, 500, 690 V Type name Type
38MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Main cubicle switch with MCCB, withdrawable circuit-breakerOptions main cubicle
39MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Apparatus cubicle for F-unitsMain cubicle switch with switch-disconnectorRated c
4MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999MNS Light F is a modular designed, factory fitted low voltageswitchgear that can
40MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999MCCB Rated current Breaking capacity 3-pole 4-polesize1)at 400, 500, 690 V Type
41MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999MCCB Rated current Breaking capacity 3-pole 4-polesize1)at 400, 500, 690 V Type
42MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999MCCB Rated current Breaking capacity 3-pole 4-polesize1)at 400, 500, 690 V Type
43MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999MCCB Rated current Breaking capacity 3-pole 4-polesize1)at 400, 500, 690 V Type
44MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999MCCB Rated current Breaking capacity 3-pole 4-polesize1)at 400, 500, 690 V Type
45MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999MCCB Rated current Breaking capacity 3-pole 4-polesize1)at 400, 500, 690 V Type
46MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999MCCB Rated current Breaking capacity 3-pole 4-polesize1)at 400, 500, 690 V Type
47MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Distribution units with switch-fuseOptionsCurrent measurement with instantaneous
48MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Rated current 1)Fuses with 3-pole 4-polemax. power dissipation Type name Type na
49MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Distribution boards with miniature circuit-breaker (MCB)OptionsProtection class
5MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Protective circuit continuityCubicle components that have been painted are assemb
50MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Miniature circuit-breaker (MCB)Options for miniature circuit-breakerSignal conta
51MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Apparatus cubicle for F-unitsDistribution boards with threaded fuses DII, 25 ANo
52MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Max motor output Fuses type gG Fuses type aMat AC3, 400 V Type name Type namekWO
53MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Max motor output Plug-in mounted MCCB > 22 kW Fixed MCCBat AC3, 400 V Manuel
54MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Max current Type nameat 80% AC1AOperation type B20 VMLC9-L63-FA3B40 VMLC30-L63-F
55MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Cover plates for unused cubicle compartmentsNo. of modules Type name1 M VML-CP61
56MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999DesignThe cubicle can be equipped with assembly plates for fixedmounting units.C
57MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999PEN(N) PEN(N)Cubical width Type namemm500 VML 402-D5600 VML 402-D6CubicleBusbar
58MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999DesignThe cubicle is supplied with main switch and max. 5 threadedfuse distribut
59MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Apparatus cubicles for threaded fuse distribution boardsCubicle width Type namem
6MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Computer requirementsComputer IBM PC or compatible withINTEL 386/486 processor.RA
60MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999GeneralThe SR-cubicle is supplied with removable SlimLine-units withswitch fuses
61MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Apparatus cubicles for SR-units (SlimLine)Cubicle width Type namemm600+400 VML 4
62MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Apparatus cubicles for SR-units (SlimLine)Type namePositioned at bottom (under n
63MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Apparatus cubicles for SR-units (SlimLine)Rated current 3-poleA Type nameSingle
64MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Distribution boards with miniature circuit-breakers (MCB)Distribution board opti
65MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Apparatus cubicles for SR-units (SlimLine)Distribution boards with threaded fuse
66MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Cover plates for used cubicle spaceNo. of modules Type name1 M VML-CP612 M VML-C
67MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999DesignThe link cubicle is used to join together MNS Light F and MNSLight SR with
ABB LV Systems ABSE-721 62 Västerås, SwedenTelephone: +46 21 346000Telefax: +46 21 346110www.abb.se/lvs1TSC2210-EN, ed. 2ReklamCenter AB, Västerås, 9
7MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Standard Type tested switchgear assemblies according to SS EN 60 439-1Test certif
8MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Transformer cubicleDesignThe fronts of the cubicles are made up of hinged doorssc
9MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999Transformer cubicleOptionsShort-circuit strength 50 kA .......