MNS Light F, MNS Light SR, Catalogue 1TSC 2210-EN, ed. 2, March 1999
Supply cubicle
Design
The supply cubicle is manufactured according to SS 436 21
31, issue 2 and in collaboration with the Swedish Electricity
Board.
The cubicle has space for incoming units and measurement
equipment.
Protection class IP21.
Current transformer insert
Current transformers are mounted on removable busbars and
are easy to change. The space is sealed and only intended for
the energy supplier's equipment. Also contains voltage fuses.
Measurement circuit breaker
The circuit-breaker, which is a MCCB, makes up the measure-
ment fuse and main switch. It is of the Sace Isomax type and
has the following functions:
- short-circuit protection in the form of a direct magnetic
overcurrent release, individually settable on each phase
- adjustable thermal overload release
- two change-over auxiliary contacts
- a shunt release
- a signal contact
The measurement circuit-breaker is available in fixed
mounted and withdrawable versions. (Withdrawable to facili-
tate disconnection, or when both measured and unmeasured
cubicles and fed from the supply and distribution cubicle.)
Switch-fuse circuit-breaker
The incoming units consists of up to six switch-fuses with
breaking on both sides of the fuse.
Connections are made from below and cables are not bent. The
height of the space from the ground is more than 600 mm.
Supply and distribution fuses
Supply fuses are changed when the unit is dead. The door for
each incoming unit is interlocked with the switch and can only
be opened with the switch in the closed position.
Sealed areas for the electricity
supplier's measurement transformers
and voltage fuses. Withdrawable
busbars mean the transformers can
be retrofitted or changes.
Space for the main switch and
instruments.
Space for up to six parallel
incoming units with switch fuses.
Free space at the bottom for the
connection of incoming supply and
distribution cables.
Switch-fuse in the supply cubicle. Due
to breaking on both sides fuse
replacement always takes place when
the unit is dead. The door is
interlocked and can only be opened
when the switch is in the closed
position.
The supply cubicle has plenty of
space for incoming cables.
800 mm